Prime Power: kW kVA 2000/2500
Standby Power: kW kVA 2200/2750
Engine gas model: H20V190ZLT-1
Cylinders and Arrangement 20 cylinders V type
Cylinder Bore, mm 1900
Piston stroke,mm 2550
Rated power, kW 2200
RPM, r/min 1000
Total piston displacement,L 144.6
Heat consumption rate kJ/kW.h 8600
Lub. oil consumption rate g/kW.h <0.6
Start method GAS
Alternator Faraday FD7E
Controller Smartgen/Deepsea HGM61100SE7320
Voltage 6300
Dimension mm 7200 x 2300 x 2780
Weight kg 28000 (open type)
(Open Type) Weight
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable load application, in
accordance with GB/T2820 -97 (eqv ISO8528);
A 10% overload capability is available for a period of 1 hour within a 12-hour period
of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power for the duration of a utility
power interruption. No overload, utility parallel or negotiated outage operation capability is available at this rating.
Rated Voltage: generally the rated power includes 380/220V, 400/230V, 415/240V, 440/254V, we make it according to client's
requirements.
Control Panel
The DSE7310 is an Auto Start Control Module and the DSE7320 is an Auto
Mains (Utility) Failure Control Module suitable for a wide variety of single,
diesel or gas,gen-set applications
Attachment (Optional Parts)
20ft Container canopy
Scientific and efficient Special sand-proof waterproof blinds with illumination.
Soundproof Canopy
(Super Silent canopy)Containerized Canopy
CHP system (Exhaust Heat Collector)
1. The unique spiral winding structure increases the turbulence effect, and the heat exchange capacity per unit area is 3-7 times that of the traditional heat exchanger.
2. High heat transfer coefficient, high heat exchanger heat transfer efficiency, good heat transfer effect, high heat transfer coefficient up to 14000W/m·k, energy saving effect is remarkable.
3. Small size. With only one-tenth of the traditional tube and shell heat exchangers, it takes up less space and reduces infrastructure and installation and maintenance costs.
4. Using a small clearance design to increase the flow rate, the heat exchanger is not easy to foul, and the use and maintenance costs
are low.
5. Advanced design concept, the length of the heat exchange tube is 3-4 times the height of the cylinder, the material stays longer and the
heat transfer is more fully.
6. Spiral-wound elastic tube bundle design can effectively eliminate pipe vibration and stress due to thermal expansion and contraction deformation.
7. Unique 90 degree connection, heat exchangers all participate in heat exchange,
no dead ends and stagnant areas, reduce fluid resistance.
8. Counter-current heat transfer, asymmetric flow design, in the vapor-liquid heat transfer field has other advantages that can not be compared with heat exchangers.
Automatic Paralleling and Gridconnect Control System
This system can connect generator sets in parallel or connect the generator set to the grid automatically.

CHP/Cogeneration/CCHP/Trigeneration

Remote Control

PMG Alternator

Oil and Water Heater

High Voltage Alternator 6.3kv and 10.5kv, High Voltage Electrical Control Cells (PT Cabinet

CT Cabinet

High Voltage outgoing cabinet

DC Panel, Groud Resistance Cabinet and low voltage distribution cabinet etc)
Remarks:

Both 50Hz and 60Hz are available.

Available in the following voltage:380V/220V,400V/230V,415V/240V,440V/254V.

Alternator brand Stamford,Leroy Somer,Marathon are optional.

Controller brand Deepsea,Comap are optional.

Special requirements for Soundproof Canopy, ATS, Parallel & Synchronization Control, CHP and Biogas Pre-treatment Machinery are optional

The data herein can vary depending on individual production
Sea-Level<1000m , Temp<40º